TM70/3-10 & i-Kontrol Console RC System
U035.3-TM70_Console_Sys
84
25.2.5 Ramps
Ramp speed is defined for each half-axis. Parameter values are shown in Table 42.
Table 42. Output Minimum-to-Maximum Ramp Time
Value
Time
Value
Time
Value
Time
Value
Time
0
No Ramp
4
0.4s
8
1.0s
12
2.0s
1
0.1s
5
0.5s
9
1.2s
13
2.5s
2
0.2s
6
0.6s
10
1.5s
14
3.5s
3
0.3s
7
0.8s
11
1.7s
15
5.0s
The parameter values are modified using EEPROM recorder.
25.2.6 PWM (Pulse Width Modulated) Frequency (Available Only for A2ICAN)
This parameter only applies to outputs that have current regulation (A2ICAN). See Table 43.
Table 43. PWM Frequency Selections
Parameter
Value
PWM Frequency
0
500Hz
1… 5
Invalid
6
33Hz
7… 255
35… 1275Hz (Parameter x 5)
The Tele-Alignment adjustments made to Output 1 are automatically set to Output 2.
25.2.7 Dither
This parameter only applies to outputs that have current regulation (A2ICAN), and only if PWM
FREQ. = 0 (5000Hz).
Dither Frequency Range 33… 255Hz
Dither Amplitude 0… 50%
The Tele-Alignment adjustments made to Output 1 are automatically set to Output 2.
25.2.8 Reset Output
This parameter allows the user to restore the analog output to its default values from the
EEPROM.